Valve Packing by Slade Inc.

Advantages

Fire Safe

  • Slade braided graphite foil is API Fire Test Certified
  • API 589 First Edition
  • API 607 Fourth Edition (modified by EXXON Specs)
  • Tested by Southwest Research Institute
  • Witnessed by 3 EXXON Engineers
  • Temperatures to 1876°F/1030°C
  • Tested at 5% of allowable standard
  • Performed under a grant from the American Petroleum Institute
  • Warning: Valves sealed with packings containing lubricants or blocking agents (PTFE) may cause secondary fires when exposed to the intense heat of a fire in another unit, which would cause packing shrinkage and leakage of flammable fluids causing a secondary fire.
  • SLADE Patented Packings: rated FIRE SAFE

Emission Safe

  • PERF Emission Standards
  • Contact Slade for documentation
  • EXX-Emission Report:
    • Emission tests, performed at a leading petroleum company's test facility in Florham Park, NJ (using PERF procedures and standards), show that Slade patented, reinforced braided graphite foil outperformed standard die-formed graphite sealing rings.
    • Slade reduced emissions by 74%.
  • Corpus Report:
    • A major Gulf Coast, USA refinery reports that 96% of the 325 valves packed with slade reported zero ppm emissions.  Most of these valves were packed in the field by inexperienced installers.
  • Cambridge Report:
    • A major USA West Coast refinery reports that after 5 years, 96% of the 282 field installed valves were at zero emissions and that the 3,000 psi hydrogen control valves never went over 9 ppm during the 5 year test. Most of these valves were packed in the field.

 All claims made herein are documented.

Valve Sealing Technology

Warranty

Valve Packing, Slade Inc, York Fluid Controls

Applications

  • Gate Valves
  • Globe Valves
  • Pinch Valves
  • Diaphram Valves
  • Needle Valves
  • Plug Valves
  • Butterfly Valves
  • Ball Valves
  • Check Valves
  • Relief Valves
  • Control Valves
  • Knife Valves

Product Selection

Product Information 

3300C – Slade’s Cost Effective Pump and Valve Packing
Reinforcement: Each yarn of graphite foil is reinforced with high strength structural carbon fiber
Temp: Non-oxidizers: -400°F/-240°C  to 5400°F/3000°C
Mild Oxidizers to 1800°F/1000°C
Pressures: Valves to 1000 PSI/70 BAR (for higher pressures, consult factory)
pH Range: 1-14
3300W: Inconel wire reinforced for higher pressures: 5000 PSI/350 BAR
3300LC: Low chloride, high purity for nuclear service 
3300LS: Low sulfur, high purity for nuclear service 
3300G – Slade’s Best All Purpose Pump and Valve Packing
Reinforcement: Corners and yarns of graphite foil reinforced with high strength structural carbon fiber
Temp: Non-oxidizers: -400°F/-240°C  to 5400°F/3000°C
Mild Oxidizers to 1800°F/1000°C
Pressures: Valves to 5000 PSI/70 BAR without end-rings
Pumps: Flush-free in many services to 4800 FPM (1400 m/min)
pH Range:
1-14
Applications: Chemicals, steam, hydrocarbons, etc.
Installation:
  1. Check clearances and dimensions
  2. Best to use no more than 5 rings in stuffing box (us Slade spacer bushings to reduce rings
  3. Cut rings on the bias (45° angle), stagger joints
  4. Compress each ring 25% (especially the first ring)
  5. Loosen gland to allow it to relax
  6. Snug the gland bolts and start the pump
3300GLC: Low chloride for nuclear service 
3300GLS: Low sulfur for nuclear service 
Advantages of Using Slade 3300G Valve Packing
Valve Packing, Slade Inc, York Fluid Controls
  1. Seals Fugitive Emissions to below 50 PPM !
  2. Puts anti-extrusion into each ring (as opposed to just top or bottom)
  3. Puts the tensile strength of graphite fiber into the sealability of flexible graphite (see next slide)
  4. Reduces inventory and cost:
    1. By eliminating die-formed rings for each size
    2. By having a few standard sizes for all valves and pumps
    3. By not ruining an entire packing set because of one ruined ring ( sets not required )
    4. In many applications, no need to remove old packing, just add ring
  5. No End-Rings required!   Puts wiping action in each ring to prevent build-up of graphite particles at top and bottom rings and the loss of volume in between
  6. Extremely high tensile strengths achieved with carbon/graphite core and corners
  7. No risk of misplacement of the anti-extrusion rings (each ring acts as an anti-extrusion device no matter where you put it).  Fewer installation errors
  8. High operating temperatures (typically: 1,800° F )
  9. Conforms to the geometry of the stuffing box and stem; undersized or worn stems and shafts easily sealed
  10. "Live-loading" not required (no weight loss at temperatures up to 1,000 degrees F).
  11. Seals pressures to 5,000 PSI in Valves, without special rings
  12. Highly polished surfaces are not required since natural, exfoliated graphite fills in the interstices of rougher surfaces, providing a lubricated surface:  graphite against graphite (recommendations are RMS. 16 to 32)
  13. Handles media within full 1-14 pH
Enviro-Foil™ Spacer Bushings
Valve Packing, Slade Inc, York Fluid Controls

New Enviro-Foil spacer bushings replace carbon bushings for Slade’s valve repair customers.

Slade’s patented technology for metallic foil inserted braiding yarns eliminates the machined carbon bushings used as spacers in stuffing boxes.


Valve Packing, Slade Inc, York Fluid Controls

EPRI (Electrical Power Research Institute) has proven that using more than five rings of packing reduces the sealing capability of all valve packings. Machined carbon bushings are used to act as space fillers to improve valve-sealing performance.

Slade’s patented technology, has lead to the development of a simpler spacer system that is more user friendly.

Available in both pre-formed rings or ‘off-the-spool.’

Also excellent as an Anti-Extrusion Ring!!!

Valve Packing, Slade Inc, York Fluid Controls

Installation

  • Check clearances and dimensions
  • Best to use no more than 5 rings in stuffing box (use DSS rings, Slade's spacer bushings, to reduce rings)
  • Cut rings on the bias (45° angle), stagger joints
  • Compress each ring 25%-30%  (use packing compressors as needed)
  • Loosen gland to allow it to relax
  • Snug the gland bolts and start the pump
Valve Packing, Slade Inc, York Fluid Controls