New solid state Chill-Out prevents low temperature damage
The new Chill-Out senses freezing temperatures within any 12 inch section along its length. It replaces fragile and difficult to install gas capillary tubes and their mechanical switches ("Freezestats"). Unlike the capillary tubes, this sensor can be installed horizontally or vertically or easily formed to fit any shaped system.
The sensor elements are available in a variety of styles including bendable aluminum tubing and ultra-flexible brass armor. The electronic shut off control can be mounted at the measuring point or within a central control box for convenient monitoring. An LED on the control box indicates a tripped condition, and a manual reset button allows the operator to quickly reinstate the system.
Standard models have a 41ºF set point with a DPDT relay; custom models can be ordered with any required trip point.
- Two sensors in one easily installed package: a solid state low temperature cut-out ("Freeze Stat") and an averaging resistance temperature sensor.
- Solid state design and rugged 3/8" diameter tubing eliminate concerns of gas leaks or kinking the capillary during installation.
- Sensitive to low temperature within any 12" segment vs. a typical 18" segment in gas filled designs.
- Mount in any direction -- horizontal installation is not required.
- Easily formed aluminum or ultra flexible brass armor sensor case.
- Relay and control circuitry self contained in rugged housing. Mounts on either side of enclosure with a locknut (included).
- Failure detection feature -- relay changes state if power is lost
- 4 to 20mA temperature loop output available with optional Temptran
|