Cooling Tower Controller Model 330 ORP
|
| |

The Model 330 allows you to control ORP levels in your cooling tower. This model features an alarm timer which prevents excessive chemical feed and a flowswitch which prevents chemical feed if there is no sample flow. For cooling tower applications only. Includes plumbing.
Specifications
| Inputs |
|
|
| Power |
|
120 VAC |
| 120/240 VAC |
|
w/-WP |
| Sensor ORP |
|
Combination glass electrode in PVC housing. |
| Flow switch |
|
Dry contact |
| Outputs |
|
|
| Relays |
|
3 Amps @ 120 VAC |
| 0-1 mA |
|
non isolated |
| 4-20 mA isolated, |
|
internal power w/-35 |
| Plumbing |
|
|
| Pressure |
|
140 psi (9.7 bar) 100°F (38°C) |
| Max. Temp. |
|
140°F (60°C) |
| Min. Flow |
|
1 gpm (3.8 Lpm) |
| Controller |
|
|
| ORP Range |
|
0-1,000 mV |
| Accuracy |
|
±5 mV |
| Resolution |
|
1 mV |
| Deadband |
|
Adjustable |
| Setpoints |
|
HIGH and LOW |
| Alarm |
|
Timer 5-90 minutes. Locks out both HIGH and LOW setpoints. |
| Ambient Temperature |
|
32-158°F (0-70°C) |
| Enclosure Rating |
|
ABS Plastic |
|
|
NEMA 4X Optional |
Ordering information
| 330 |
|
ORP controller for direct and reverse feed setpoints, 0-1,000 mV range, a feed limit timer with push button reset, flowswitch, sensor, power cord, outlets and a digital display. |
| ENCLOSURE OPTIONS (optional) |
| -WP |
|
Watertight enclosure with 120/240 VAC 50/60 Hz power switch. ½ inch conduit knockouts. No outlets or power cord. |
| PLUG-IN OUTPUT OPTIONS (optional, select one only) |
| -35 |
|
Isolated 4-20 mA output for remote data acquisition. |
| -39F |
|
Frequency output contact for electronically pulsed chemical pump. |
| -39P |
|
Percent on-time modulating contact for solenoid chemical feed systems. |
| -42 |
|
HIGH/LOW alarm contacts with adjustable setpoints. |
| -44 |
|
Isolated 4-20 mA output plus High/ Low alarms. |
|
|
|