cooling,tower,controller,model,330,orp,lakewood,instruments

Cooling Tower Controller Model 330 ORP


Cooling Tower Controller Model 330 ORP

 

Product Information

The Model 330 allows you to control ORP levels in your cooling tower. This model features an alarm timer which prevents excessive chemical feed and a flowswitch which prevents chemical feed if there is no sample flow. For cooling tower applications only. Includes plumbing.

Specifications
Inputs
Power 120 VAC
120/240 VAC w/-WP
Sensor ORP Combination glass electrode in PVC housing.
Flow switch Dry contact
Outputs
Relays 3 Amps @ 120 VAC
0-1 mA non isolated
4-20 mA isolated, internal power w/-35
Plumbing
Pressure 140 psi (9.7 bar) 100°F (38°C)
Max. Temp. 140°F (60°C)
Min. Flow 1 gpm (3.8 Lpm)
Controller
ORP Range 0-1,000 mV
Accuracy ±5 mV
Resolution 1 mV
Deadband Adjustable
Setpoints HIGH and LOW
Alarm Timer 5-90 minutes. Locks out both HIGH and LOW setpoints.
Ambient Temperature 32-158°F (0-70°C)
Enclosure Rating ABS Plastic
NEMA 4X Optional

Ordering information
330   ORP controller for direct and reverse feed setpoints, 0-1,000 mV range, a feed limit timer with push button reset, flowswitch, sensor, power cord, outlets and a digital display.
ENCLOSURE OPTIONS (optional)
-WP   Watertight enclosure with 120/240 VAC 50/60 Hz power switch. ½ inch conduit knockouts. No outlets or power cord.
PLUG-IN OUTPUT OPTIONS (optional, select one only)
-35   Isolated 4-20 mA output for remote data acquisition.
-39F   Frequency output contact for electronically pulsed chemical pump.
-39P   Percent on-time modulating contact for solenoid chemical feed systems.
-42   HIGH/LOW alarm contacts with adjustable setpoints.
-44   Isolated 4-20 mA output plus High/ Low alarms.

 


Site Designed And Maintained By Panther Marketing & Design