1/8 DIN Temperature Controller Heat/Cool Controllers

1/8 DIN, Temperature Controller, Heat/Cool ControllersFuzyPro 1 /8 DIN Temperature Controller Heat/Cool Controllers are designed to provide precise control with a quick and easy set up procedure. SMT and microprocessor technology provides all these features plus reliability and economy. LED index indication allows full viewing and selection of parameters.

The dual display allows set point and process value visibility at all times. An advanced software algorithm automatically calculates all PID parameters to eliminate complicated manual tuning efforts. Automatic tuning can be bypassed if manual tuning is preferred. An open-loop, manual mode can be initiated if the sensor fails. Front panel electronic calibration sensor linearization self-diagnostic capabilities and cold junction compensation are all performed by the single chip microprocessor. The in-panel depth is only 2-1/2".

FuzyPro 1 /8 DIN Temperature Controller Heat/Cool Controllers Features:

  • Automatic tuning of PID parameters
  • Selectable input
  • Dual heating and/or cooling outputs with 2 alarms
  • ºF or ºC display. Dual display. Sealed mylar front panel
  • Security code protection, automatic manual mode operation
  • All control parameters adjustable from front panel
  • 3 year warranty. 2-1 /2" in panel depth

  • FuzyPro 1 /8 DIN Temperature Controller Heat/Cool Controllers Specifications:

    INPUT
    Thermocouple Type J,K.T.B.E,R,S,N selectable
    RTD PT 100ohm (DIN or JIS)
    Linear -10-60mV Configurable input or voltage or current
    Display Temperature or engineering units
    OUTPUTS Single output with 2 optional independent alarms
    Heating and cooling outputs with 2 optional Alarms
    Relay SPST relay rated 3A, 240V maximum resistive load
    Pulsed Voltage 32VDC,2OmA maximum ohms
    Current 4-20mA,0-20mA maximum load 500 ohms
    Voltage 0-10V minimum load 500K ohms
    Alarms 8 selectable modes each alarm
    SPST relay(s) rated 2A, 240V maximum resistive load.

    CONTROL FEATURES
    Temp Range Selectable Set Point: -1999-3182F/-1128-1750C
    Alarm Set Point Full Range Adjustable
    Control Modes Controls can be configured as On/Off Proportional (P)
    Proportional with manual reset                             
    Proportional/Integral (PI) Proportional                             
    Derivative (PD)                             
    Proportional/Integral/Derivative (PID)                             
    Heating and Cooling Proportional Band: 0-100% of span
    Integral (Reset) 0-3600 seconds
    Derivative(Rate) 0-1000 seconds
    Anti-Reset Wind-up Inhibits integral action outside of proportional band.
    Cooling Adjustable deadband from-10 to + 10% of cooling proportional band
    Manual Mode Configurable as open loop control should sensor no longer function
    Cycle Time 0-120 seconds
    Sensor Break Protection Configurable status of control and alarms
    Control Action Selectable-Direct action for cooling Reverse action for heating

    INDICATION
    Display 4 digit red 5/8" LED Process Value Display.
    Green 1.2" LED Set Value display
    Selectable decimal placement for normal or high resolution display
    Example 0000, 000.0, 00.00 or 0.000
    F/C Selectable with 2 LED indicators
    Sample Rate 250 milliseconds
    Power Supply 90-26OVAC, 50/60Hz Consumption: less than 5VA
    Data Retention l0 years (EEPROM)
    Control Stability + -0.15% of full scale
    Accuracy + -0.25% of range: + -1 c or 0.5C in high resolution
    Cold Junction Compensation 0.1% ambient
    External Resistance 100 ohms maximum
    Common Mode Rejection 120dB
    Normal Mode Rejection 60dB
    Input Impedance 10M ohms
    Operating Temperature 14-122ºF (-10-50ºC)
    Humidity 0-90% RH(non-condensing)
    Insulation 20M ohm minimum (5OOVDC)
    Breakdown 2OOVAC, 50/60Hz 1 minute
    Vibration 10-55Hz amplitude 1 mm
    Shock 200m/c (20g)