Continous,Level,Transmitter

Continuous Level Transmitter
from Dwyer Instruments

Process Control Index

 Series CRF Continuous Level Transmitter Loop Powered, 4-20 mA Output, RF Admittance Technology

  Continuously monitor the level of liquids and slurries, without worry of false signals as a result of material build-up. Loop powered Series CRF delivers a 4-20 mA isolated output signal proportional to the height of material in a tank or holding vessel. Continuous level transmitter can be field calibrated to fit your specific application. Integral electronics and two-wire design simplify installation. Probes should be mounted vertically and are easily trimmed to shorter lengths where required. When mounting in nonmetallic or horizontal tanks, a separate grounding rod must be used. Consult factory regarding mounting flange and grounding rod assemblies.

PHYSICAL DATA

Supply Voltage:   18 to 30 VDC
Output Signal:   4-20 mA, 2-wire, isolated
Maximum Loop Resistance:   600W @ 24 VDC
Zero Range:   0 to 500 pF
Repeatability:   0.1% FS
Operating Temperature Range:   -10 to 180°F (-23 to 82°C)
Mounting:   ¾" NPT(M), Optional flange mounting
Conduit Opening:   ½" NPT (F)
Probe Enclosure:   NEMA 4, 7 & 9, epoxy coated aluminum
Wetted Materials:   316SS, Teflon®
Power Consumption:   6VA
Span Range:   25 to 2200 pF
Linearity:   0.3% of range
Weight:   7.25 lbs. (3.29 kg)

APPLICATIONS


Alcohols, wastewater, oils, polymers, acids, caustics, pulp, slurries, wood chips, water-based products in tanks, bins, or other vessels.

Continuous Level Transmitter
from Dwyer Instruments

Site Designed By Panther Marketing & Design