Hydronic Manometer

Hydronic Manometer

 Alnor AirGard® Air Flow Monitors

HM 670/HM 680 Hydronic Manometer

Alnor hydronic manometers measure fluid pressure (differential and guage), temperature, and calculate flow rate (HM680) to test and balance heating/cooling systems or check pump performance.


NOTE: HM650 Hydronic Manometer (discontinued Jan 1, 2005)

Feature

Benefit

Stainless steel and brass wetted materials

Corrosion resistant for long trouble free life

Separate differential and gauge sensors

More accurate pressure measurements (1% of reading)

Automatic zeroing

Ensures accurate, repeatable readings without user interaction

Integral flow calculations (HM680)

Saves time, no need to use circular slide rules

Two-position, four-way valve

Easier operation, fewer manual connections and reconnections

1% accuracy

More accurate readings

Rechargeable NiMH batteries

Long life, more charging cycles than NiCad batteries

Internal and External battery charger

Charge batteries in the meter or externally

Integral flow measurement (HM680)

Virtually eliminate the need for manual slide rule calculations, saves time

Advanced calculations (HM680)

One instrument does it all for you, eliminate the need for separate calculators, slide rules, etc.

Large easy-to-read display

Simultaneously read low side, high side, differential pressure and temperature without switching screens- saves time



Frequently Asked Questions

Q: I only want to measure pressures and don’t care about flow, which model should I order?
A: If you are only interested in measuring pressures, then the model HM670 is the model you should order.


Q: What is the difference between the HM670 and HM680?
A: The HM670 is designed to perform gauge pressure, differential pressure, and temperature (with optional probe) measurements. The HM680 also calculates flow, differential temperature, BTU/Hr, pump impeller diameter size, brake horsepower and Cv (Kv). The HM680 also comes standard with a temperature probe.


Q: How is flow calculated with the HM680?
A: The operator enters the valve or other flow element Cv (Kv) factor. The HM680 measures the differential pressure, and temperature to calculate a temperature compensated flow using an industry standard flow equation.


Q: What if the hydronic system contains some other fluid instead of 100% water?
A: The user can change the specific gravity of the fluid to compensate for other system fluids.


Q: How many Cv (Kv) factors can I enter?
A: The HM680 has storage capacity for 100 separate factors.


Q: Can I customize the test ids and Cv (Kv) factors?
A: Yes, you can designate up to a 9 character custom test id and Cv (Kv) factor.


Q: How long is the warranty?
A: Two years


Q: How often should it be recalibrated?
A: Alnor recommends annual recalibration. The NIST-traceable Calibration Certificate has a 12 month expiration date.


Q: I use this meter in a wet environment. How resistant to water are these meters?
A: The HM670 and HM680 were designed to be water and splash resistant. A sealing gasket is used between the two case halves.


Q: What type of pressure sensors are used in the HM670/HM680? Are they designed to work with liquid media?
A: Yes, the new HM670 and HM680 use only stainless steel or brass wetted materials designed for continuous liquid contact. and are very corrosion resistant.


Q: Can I use these meters for air applications instead of liquid?
A: Yes, air is also a fluid.


Q: What is the maximum pressure that I can measure?
A: The HM670 and HM680 will measure up to 300 psi (2068 KPa).


Q: How soon can I get one?
A: Lead time is two weeks.


Hydronic Manometer