TNPL Single Shot Timers For IC Digital Timing Circuits
TNPL Single Shot Timers For IC Digital Timing Circuits
|
|
 |
TNPL Timers
The TN Single Shot on Make units meet the needs of
customers who require IC digital timing circuits with octal, magnal round and QC bases for
plug-in installation. The units are available in SPDT, DPST and DPDT relay forms up to 10
amp with fixed or adjustable time periods.
|
Timing Mode
Power must be applied to the input voltage
terminals continuously. Upon closure of a Normally Open (N.O.) external initiate switch,
the load is instantaneously energized and the time delay cycle starts.
Maintained closure or actuation of the external initiate switch during the delay
cycle will not affect the time delay period.
When the delay period expires, the timer will reset to its original position and
the timer is ready for another cycle.
|
 |
|
FEATURES |
-
CMOS IC digital timing
-
Multi-board construction
-
Relays are sealed
-
Proven circuitry
-
Standard octal (8 pin), magnal (11 pin) plug-ins
or 4.75 mm (.187") blade terminal mountings
- Fixed or variable time adjustment
|
-
Optional remote time adjustment
-
Timing ranges from .05 to 1000 seconds
standard (special time settings and ranges
up to 72 hours also available)
-
0.1% Repeat accuracy
- 100% Operational testing before shipping
|
| BASIC WIRING AND DIMENSIONS |
 |
| SPECIFICATIONS |
Input Voltages:
- VAC: 12, 24, 120,230,50/60/ Hz
- VDC: 12, 24
Operating Voltage: ±20% of nameplate voltage
Relay Contact Ratings: 5 amps DPDT, 10 amp DPDT optional
Repeat Accuracy: ±0.1% under fixed operating conditions
Reset Time: 50 milliseconds
Tolerances: Fixed: ±10%, Optional: ±5%, ±1%
Variable: +20%, -0 Optional:+10%, -0%
Note: Tolerances on variable units are with respect to
upper limit only. Timers with time periods greater than
10 sec. will have a 100 to 1 ratio, i.e., 1 to 100 seconds, 30 to
3000 seconds. Timers with time periods less than 10 sec. will have a 10 to 1 ratio, i.e., .99 to 9.9 seconds, .5 to 5 seconds.
|
|
Life Expectancy:
- Mechanical: 1 million operations
- Electrical: Up to 100,000 operations at full current load
Protection:
- Polarity Protection: All DC units have reverse polarity protection
- Transient Protection: 25 joules
Temperature Ranges:
- Storage: -40°C + 85°C
- Operating: -25°C to +85°C
Housing Material: High Impact, UL approved black Lexan
|
| SELECTION PROCEDURE
|
| Mode of Operation |
Series |
Input Voltage |
Time Ranges |
Tolerance |
Time Adjust. Method |
Base Style |
Options |
Single Shot
On Make with
Isolated Cntrl. Sw.
or Input
Volt Cntrl. Sw. |
TNPL |
1 120 VAC
2 230 VAC
3 24 VAC
4 24 VDC
7 12 VDC
8 Special AC
9 Special DC
|
VARIABLE TIME PERIODS |
X Standard
(Fixed: ±10%
Variable: +20% 10%)
E Optional
(Fixed: ±5%)
F Optional
(Fixed: ±1%)
G Optional
(Adjust.: +10%, -0%)
|
A Variable knob on timer
B Variable with external peotentiometer, AOT supplied
D Factory fixed time
C Factory fixed time with customer supplied resistor
|
1 8 pin round octal base
2 11 pin round magnal
3 11 pin spade .187 quick connect
|
X Standard 5 amps
H 10 amps (8 amps UL Recognized for USA and Canada)
|
0001 .1 to 1 sec.
0010 .1 to 10 sec.
0100 1 to 100 sec.
1000 10 to 1000 sec.
Any range up to 72 hours available on special order |
| FIXED TIME PERIODS |
Specify time in full seconds or hours
followed by the letter "S" or "H" and the decimal amount of the main time unit
and the decimal amount of the main time unit.
Examples: 5S5 is 5.5 secs.
5H5 is 5.5 hours |
|
|