Digital Plug-In Single Shot Timers - TNP Timers
Digital Plug-In Single Shot Timers - TNP Timers
|
|
 |
TNP Timers
The TNP Single Shot on Make units
meet the needs of customers who require IC digital timing circuits with octal,
magnal round and QC bases for plug-in installation. The units are available in
SPDT, DPST and DPDT relay forms up to 10 amp with fixed or adjustable time periods.
|
Timing Mode
Power must be applied to the input voltage terminals
continuously. Upon closure of an isolated Normally Open (N.O.) external initiate switch,
the load is instantaneously energized and the time delay cycle starts.
Maintained closure or actuation of the external initiate switch during the delay cycle
will not affect the time delay period.
When the delay period expires, the timer will reset to its original position and the
timer is ready for another cycle.
|
 |
|
FEATURES |
-
CMOS IC digital timing
-
Multi-board construction
-
Relays are sealed
-
Proven circuitry
-
Standard octal (8 pin), magnal (11 pin) plug-ins
or 4.75 mm (.187") blade terminal mountings
- Fixed or variable time adjustment
|
-
Optional remote time adjustment
-
Timing ranges from .05 to 1000 seconds
standard (special time settings and ranges
up to 72 hours also available)
-
0.1% Repeat accuracy
- 100% Operational testing before shipping
|
| BASIC WIRING AND DIMENSIONS |
 |
| SPECIFICATIONS |
Input Voltages:
- VAC: 12, 24, 120,230,50/60/ Hz
- VDC: 12, 24
Operating Voltage: ±20% of nameplate voltage
Relay Contact Ratings: 5 amps DPDT, 10 amp DPDT optional
Repeat Accuracy: ±0.1% under fixed operating conditions
Reset Time: 50 milliseconds
Tolerances: Fixed: ±10%, Optional: ±5%, ±1%
Variable: +20%, -0 Optional:+10%, -0%
Note: Tolerances on variable units are with respect to
upper limit only. Timers with time periods greater than
10 sec. will have a 100 to 1 ratio, i.e., 1 to 100 seconds, 30 to
3000 seconds. Timers with time periods less than 10 sec. will have a 10 to 1 ratio, i.e., .99 to 9.9 seconds, .5 to 5 seconds.
|
|
Life Expectancy:
- Mechanical: 1 million operations
- Electrical: Up to 100,000 operations at full current load
Protection:
- Polarity Protection: All DC units have reverse polarity protection
- Transient Protection: 25 joules
Temperature Ranges:
- Storage: -40°C + 85°C
- Operating: -25°C to +85°C
Housing Material: High Impact, UL approved black Lexan
|
| SELECTION PROCEDURE
|
| Mode of Operation |
Series |
Input Voltage |
Time Ranges |
Tolerance |
Time Adjust. Method |
Base Style |
Options |
| Single Shot On Make |
TNP |
1 120 VAC
2 230 VAC
3 24 VAC
4 24 VDC
7 12 VDC
8 Special AC
9 Special DC
|
VARIABLE TIME PERIODS |
X Standard
(Fixed: ±10%
Variable: +20% 10%)
E Optional
(Fixed: ±5%)
F Optional
(Fixed: ±1%)
G Optional
(Adjust.: +10%, -0%)
|
A Variable knob on timer
C Factory fixed time
|
1 8 pin round octal base
2 11 pin round magnal
3 11 pin spade .187 quick connect
|
X Standard 5 amps
H 10 amps (8 amps UL Recognized for USA and Canada)
|
0001 .1 to 1 sec.
0010 .1 to 10 sec.
0100 1 to 100 sec.
1000 10 to 1000 sec.
Any range up to 72 hours available on special order |
| FIXED TIME PERIODS |
Specify time in full seconds or hours
followed by the letter "S" or "H" and the decimal amount of the main time unit
and the decimal amount of the main time unit.
Examples: 5S5 is 5.5 secs.
5H5 is 5.5 hours |
|
|